AI, 16 Bit, U, ±10V

AI 2 x U, ±10 V, 0-10 V, 1-5 V, Iso., 16 Bit
AI 2 x U, ±10 V, 0-10 V, 1-5 V, Iso., 16 Bit

AI 2x U, ±10 V, 0-10 V, 1-5 V, Iso., 16 Bit

Parameters for the module

  • Diagnostic alarm: On | Off
  • Overflow/underflow diagnosis: On | Off
  • Representation values: SIMATIC* S7 | SIMATIC* S5 | INT16

 

Parameters for each channel

  • Wire break detection (only for 1 ... 5 V): On | Off
  • Interference frequency suppression: None | 10 Hz | 50 Hz | 60 Hz | 400 Hz
  • Measuring ranges: Deactivated | 0 ... 10 V | 1 ... 5 V | ±10 V | ±5 V | ±2.5 V
  • Limit value alarms enabled: On | Off
  • Upper/lower limit: 16 bit analog value (±27648)

 

Channel LED signals

Flashing red light

Parameter assignment error on channel

Solid red light

Reading overflow/underflow or wire break

Flashing green light

Reading within overrange

Solid green light    

Channel configured, normal reading

 

Off 

Channel disabled or module not yet configured


  • Channels electrically isolated from each other and from the backplane bus
  • Measuring ranges 0 ... 10 V, 1 ... 5 V, ±10 V, ±5 V, ±2.5 V, individually configurable for each channel
  • Measurement resolution: up to 15 bits + sign
  • Diagnostic messages
  • Wire break detection (for 1 ... 5V)
  • Limit value alarms for each channel
  • A bi-color LED (blue/red) indicates the module operating status and any malfunctions
  • Red/green bi-color LEDs (one for each channel) indicate the channel status
  • 2 analog inputs for measuring voltage
  • 2 process input words
Download PDF datasheet
General information
Order number600-252-7BB01
Article nameAI 2x U ,±10 V, 0–10 V, 1–5 V, Iso., 16 bit
Scope of deliveryAI 2x U ,±10 V, 0–10 V, 1–5 V, Iso., 16 bit
Dimensions (DxWxH)110 x 14 x 73 mm
WeightApprox. 70 g
Number of inputs2
Electrical isolation
from the backplane busYes
Between the channelsYes
InternalMax. 140 mA
Power dissipationMax. 1 W
Measuring ranges / load resistance0 ... 10 V / 2 Mohms, 1 ... 5 V / 2 Mohms, ±10 V / 2 Mohms, ±5 V / 2 Mohms, ±2.5 V / 2 Mohms
Measuring methodIntegration
Measurement resolution15 bits + sign
Interference frequency suppressionNone | 10 Hz | 50 Hz | 60 Hz | 400 Hz
Refresh rate / conversion rateDepends on the interference frequency suppression setting being used:
None: 2 ms
400 Hz: 8 ms
60 Hz: 51 ms
50 Hz: 60 ms
10 Hz: 160 ms
DiagnosesUpper measuring range limit exceeded (overflow), lower measuring range limit fallen below (underflow), wire break (for 1 ... 5 V only), parameter assignment error
Process alarmsUpper and lower limit per channel
Error limits
Operational error limit in the entire temperature range±0.2 % relative to the nominal range
Basic error limit at 25 °C±0.1 % relative to the nominal range
Temperature error±0.005 %/K relative to the nominal range
Linearity error±0.05 %/K relative to the nominal range
Repeating accuracy in steady state at 25 °C±0.05 %/K relative to the nominal range
Parameter configuration length14 bytes
General error indicatorRed LED
Hot-swap capableYes
Ambient conditions
Ambient temperature0 °C … +60 °C
Transport and storage temperature-20 °C … +80 °C
Relative air humidity95 % r H without condensation
Protection ratingIP 20
CertificationsCE, UL
UL
Surrounding Air Temperature0 °C … +60°C
Pollution degree2
CE
Noise immunityDIN EN 61000-6-2 “EMC Immunity”
Interference emissionDIN EN 61000-6-4 “EMC Emission”
Vibration and shock resistanceDIN EN 60068-2-6:2008 „Vibration“, DIN EN 60068-2-27:2010 „Shock"
RoHSYes
REACHYes

Technical Documentation

 NameVersionSizeTags
TB20, Manual Modules 15 8 MBTB20, Manual Modules

Flyers

 NameVersionSizeTags
Flyer, TB20 IO-system for numerous applications 11-2017 4 MBTB20 IO-system for numerous applications

Planning Tools

 NameVersionSizeTags
AI 2x U, ±10 V, 0-10 V, 1-5 V, Iso., 16 Bit, STEP Files 3 MBAI 2x U, ±10 V, 0-10 V, 1-5 V, Iso., 16 Bit, STEP Files
Spam-Schutz

* SIMATIC is a registered trademark of Siemens AG.