TB20-C, Bus coupler
PROFIBUS-DP
PROFIBUS-DP
The PROFIBUS-DP bus coupler is designed to connect a PROFIBUS bus to TB20 peripheral modules. It supports the DP-V0 and DP-V1 protocols.
It will recognize all connected peripheral modules and assign each module the corresponding inputs/outputs from the process image table.
A functioning TB20 configuration will always require a bus coupler and at least one peripheral module, but can accommodate up to 64 modules of any kind connected in series with the bus coupler. The bus coupler supports hot-swap for replacing modules during operation.
Bit packing:
Starting with firmware version 1.20, the states of 2-bit and 4-bit I/O modules can be packed together in bytes, making it possible to take full advantage of all the space in the process image table.
Parameters
- Diagnostic alarm: On | Off
- Process alarm: On | Off
- Pull/plug alarm: On | Off
- Startup when expected/actual configuration differ: On | Off (hot-swaping allowed: Yes | No)
- Identifier-related diagnostics: On | Off
- Submodule status: On | Off
- Channel-related diagnostics: On | Off
- Modules can be replaced during operation (hot-swapping)
- 24 VDC power supply
- Integrated power supply unit for powering peripheral modules (2.5 A)
- Supplies the system’s I/O voltage (24 VDC)
- USB device port for online diagnostics, configuring parameters, setup, and firmware updates with TB20 ToolBox
- TB20 ToolBox simulation for setting up the I/O system without a higher-level controller in order to test the system`s operation (I/O check)
- PROFIBUS DP slave as defined in EN 50170/IEC 61158
- Supports all PROFIBUS baud rates
- DP-V0 and DP-V1 support
- Up to 64 peripheral modules
- Up to 244 bytes of input data and 244 bytes of output data
- One class 1 master connection with 240 bytes of payload data
- Up to three class 2 master connections with 240 bytes of payload data (as a DP-V1 slave)
- I&M data
- 3 LEDs, one of them bi-color
- Concealed "factory reset" switch for restoring the module to its factory settings
General information | ||
---|---|---|
Order number | 600-151-1AA11 | |
Article name | TB20-C, PROFIBUS-DP bus coupler | |
Scope of delivery | Bus coupler PROFIBUS-DP, 24 V power supply connector, bus cover element, base module | |
Dimensions (DxWxH) | 73 x 35 x 110 mm | |
Weight | Approx. 115 g | |
PROFIBUS interface | ||
Number | 1 | |
Protocol | PROFIBUS DP/V0 & DP/V1 | |
Transmission rate | 9.6 Kbaud ... 12 Mbaud, automatic detection | |
I/O image size | 244/244 bytes | |
Parameter configuration length | 244 bytes | |
Interface | RS485 | |
Connection | 9-pin D-sub female connector | |
USB interface | ||
Number | 1 | |
Protocol | Full-speed USB 1.1 device | |
Connection | Mini-USB | |
Isolation voltage | 1.5 kV | |
Electrical isolation | Yes | |
Number of modules that can be connected in series | 64 | |
Voltage supply | 24 VDC, 18–28 VDC | |
Current draw | ||
Current draw without modules (internal) | 75 mA | |
Power supply for modules | 5 V DC, max 2.5 A | |
Power dissipation | Max. 8 W | |
Mounting position | Any | |
Ambient conditions | ||
Ambient temperature | 0 °C … +60 °C | |
Transport and storage temperature | -20 °C … +80 °C | |
Relative air humidity | 95 % r H without condensation | |
Protection rating | IP 20 | |
Certifications | CE, UL | |
UL | ||
Surrounding Air Temperature | 0 °C … +50 °C | |
Pollution degree | 2 | |
CE | ||
Noise immunity | DIN EN 61000-6-2 “EMC Immunity” | |
Interference emission | DIN EN 61000-6-4 “EMC Emission” | |
Vibration and shock resistance | DIN EN 60068-2-6:2008 „Vibration“, DIN EN 60068-2-27:2010 „Shock" | |
RoHS | Yes | |
REACH | Yes |
Technical Documentation
Name | Version | Size | Tags | |
---|---|---|---|---|
TB20, Manual PROFIBUS-DP Bus Coupler | 5 | 10 MB | ||
EG Declaration of Confirmity | 04-2020 | 55 KB | EG Declaration of Confirmity |
Flyers
Name | Version | Size | Tags | |
---|---|---|---|---|
Flyer, TB20 IO-system for numerous applications | 11-2017 | 4 MB | TB20 IO-system for numerous applications |
Software
Name | Version | Size | Tags | |
---|---|---|---|---|
TB20, GSD file for PROFIBUS-DP Bus Coupler | 1.48 | 75 KB | ||
TB20-ToolBox V2 Setup | V2.10.004 | 28 MB | History
================================= V2.10.004 12.11.2020 V2.10.002 09.09.2020
|
TB20-ToolBox, TB20, Toolbox |
Drivers
Name | Version | Size | Tags | |
---|---|---|---|---|
TB20, USB Driver | 1.20 | 7 KB | TB20, USB Driver |
Planning Tools
Name | Version | Size | Tags | |
---|---|---|---|---|
TB20, Macros for EPLAN Electric P8* from V2.0 in EDZ format | 07.02.2018 | 84 MB | ||
TB20, STEP files | 1.00 | 8 MB |
The 24 V power supply connector, the bus cover element, and the base module are included as standard.
“TB20 ToolBox” makes it easy to plan the system. Integrated terminal mapping, system width calculations, and current-carrying capacity monitoring all make it possible to quickly design systems without making any mistakes.