DIO, DC 24 V, 500 mA

DIO 2 x In/2 x Out DC 24 V, 500 mA
DIO 2 x In/2 x Out DC 24 V, 500 mA

DIO 2x In/2x Out DC 24 V, 500 mA

  • 24 V DC input voltage
  • Can accommodate 2-wire proximity sensors
  • 24 V DC output voltage
  • 500 mA output current per channel
  • A blue LED indicates the module's operating status
  • Green LEDs (one for each output) indicate the output status
  • 2 inputs, electrically isolated from the backplane bus
  • 2 outputs, electrically isolated from the backplane bus

Download PDF datasheet
General information
Order number 600-230-0AD01
Article name DIO 2x In/2x Out DC 24 V, 500 mA
Scope of delivery DIO 2x In/2x Out DC 24 V, 500 mA
Dimensions (DxWxH) 110 x 14 x 73 mm
Weight Approx. 70 g
Number of inputs 2
Input characteristic curve Type 2, EN 61131-2
Reverse polarity protection for inputs Yes
Input voltage
For signal "0” - 3 V … 9 V
For signal "1” 12 V … 30 V
Number of outputs 2
Electrical isolation
from the backplane bus Yes
Between the channels No
Supply voltage UP, US
Rated value 24 V DC
Ripple USS max. 3.6 V
Permissible range (with ripple) 20 … 30 V
Voltage for t < 10 ms 50 V
Output current
Rated value 500 mA
Leakage current Max. 0.5 mA
Output short-circuit protection Electronic, for each individual channel
Inductive cutoff voltage limit -48 V
Current draw
External Max. 10 mA + load
Internal Max. 25 mA
Hot-swap capable Yes
Ambient conditions
Ambient temperature 0 °C … +60 °C
Transport and storage temperature -20 °C … +80 °C
Relative air humidity 95 % r H without condensation
Protection rating IP 20
Certifications CE, UL
UL
Surrounding Air Temperature 0 °C … +60°C
Pollution degree 2
CE
Noise immunity DIN EN 61000-6-2 “EMC Immunity”
Interference emission DIN EN 61000-6-4 “EMC Emission”
Vibration and shock resistance DIN EN 60068-2-8:2008 “Vibration”, DIN EN 60068-27:2010 “Shock“
RoHS Yes
REACH Yes

Technical Documentation

 Name Version Size Tags
TB20, Manual Modules 13 17 MB