DO, Relais

DO 2 x Relais, 5 A, AC 230 V, Wechsler
DO 2 x Relais, 5 A, AC 230 V, Wechsler

DO 2x relays, 5 A, AC 230 V, changeover

  • Dry contact switching
  • 5 A output current per relay
  • Up to 230 V AC switching voltage per relay
  • Switching operation counter: two input words (switching operations *1,000)
  • Transient filter for protection against high-frequency relay switching (10 Hz)
  • A blue LED indicates the module's operating status
  • Green LEDs (one for each output) indicate the output status
  • Two changeover relays

Download PDF datasheet
General information
Order number 600-222-0AB01
Article name DO 2x relays, 5 A, AC 230 V, changeover
Scope of delivery DO 2x relays, 5 A, AC 230 V, changeover
Dimensions (DxWxH) 110 x 14 x 73 mm
Weight Approx. 80 g
Number of outputs 4 (two changeover relays)
Electrical isolation
from the backplane bus Yes
Between the channels Yes
Supply voltage UP, US
Rated value 24 V DC
Ripple USS max. 3.6 V
Permissible range (with ripple) 20 … 30 V
Voltage for t < 10 ms 50 V
Current draw
External Max. 30 mA
Internal Max. 30 mA
Relays
Number 2
Max. continuous current / max. inrush current 5 A/10 A
Rated voltage / max. switching voltage 250 V AC/400 V AC
Max. switching power for utilization category AC-1 1500 VA
Max. switching power AC15 (230 V AC) 300 VA
Single-phase motor load, AC3 – running (230 V AC) 0.185 kW
Max. switching current for utilization category DC-1: 30/110/220 V 6/0.2/0.12 A
Min. switching capacity 500 mW (12 V/10 mA)
Mechanical life 10 * 106 switching operations
Electrical life for utilization category AC-1 60000 switching operations
Dielectric strength, coil to contact 6 kV (8 mm)
Dielectric strength across open contacts 1000 V AC
Max. switching frequency (internal protection) 10 Hz
Hot-swap capable Yes
Ambient conditions
Ambient temperature 0 °C … +60 °C
Transport and storage temperature -20 °C … +80 °C
Relative air humidity 95 % r H without condensation
Protection rating IP 20
Certifications CE, UL
UL
Surrounding Air Temperature 0 °C … +60°C
Pollution degree 2
CE
Noise immunity DIN EN 61000-6-2 “EMC Immunity”
Interference emission DIN EN 61000-6-4 “EMC Emission”
Vibration and shock resistance DIN EN 60068-2-8:2008 “Vibration”, DIN EN 60068-27:2010 “Shock“
RoHS Yes
REACH Yes