Counter
1x Counter 24 V, 500 kHz, 32 Bit
Counters are used to detect pulses that are faster than a controller’s cycles, i.e., signals that the controller will be unable to detect properly and that therefore need to be pre-processed.
Choose variant
Counters are used to detect pulses that are faster than a controller’s cycles, i.e., signals that the controller will be unable to detect properly and that therefore need to be pre-processed.
The counter module detects the edges of 24 V signals as pulses. The impulses can be counted or converted into a frequency, rotational speed, or period. The counter module features an additional 24 V input and a 24 V output for a direct response to start pulses and to quick system state changes.
Capturing modes
- Pulse & direction
- Rotary encoder with single evaluation
- Rotary encoder with double evaluation
- Rotary encoder with quadruple evaluation
Counting methods
- Continuous counting
- Once-only counting
- Periodic counting
Measuring mode
- Frequency measurement
- Rotational speed measurement
- Period measurement
Programmable input
- PLC input
- Approval (HW gate)
- Synchronization
- Periodic synchronization
- Latch
- Latch & retrigger
- Can be inverted
Programmable output
- PLC output
- Count >= Reference value
- Count <= Reference value
- Count = Reference value
- Can apply a substitute value at STOP
Note: Individual modules cannot be combined with the IO systems of other manufacturers.
- 32-bit counter
- Up to 500 KHz (4-fold evaluation)
- Accommodates 24 V incremental encoders and proximity sensors
- Filters: 10 kHz | 50 kHz | 100 kHz | 500 kHz
- All inputs can be inverted
- Limits for counter and measured readings
- Hysteresis for input
- Pulse duration for output
- Refresh rate / averaging time for measuring mode
- 8 bytes of input data (count and status)
- 8 bytes of output data (preset count and commands)
General information | ||
---|---|---|
Order number | 600-300-7AA01 | |
Article name | 1x Counter 24 V, 500 KHz, 32 bit | |
Scope of delivery | 1x Counter 24 V, 500 KHz, 32 bit | |
Dimensions (DxWxH) | 110 x 14 x 73 mm | |
Weight | Approx. 70 g | |
Input voltage | 24 V DC | |
Electrical isolation | ||
from the backplane bus | Yes | |
Between the channels | No | |
Current draw | ||
External | Max. 10 mA + load | |
Internal | Max. 86 mA | |
Power dissipation | 0.8 W | |
Input characteristic curve | Type 2, EN 61131-2 | |
Output current | ||
Rated value | 500 mA | |
Leakage current | Max. 0.5 A | |
Short-circuit protection | Electronic | |
Parameter configuration length | 16 bytes | |
Number of counters | 1 | |
Counter bit depth | 32 bits | |
Counting frequency per channel | Max. 500 kHz (for 4x evaluation) | |
Hot-swap capable | Yes | |
Ambient conditions | ||
Ambient temperature | 0 °C … +60 °C | |
Transport and storage temperature | -20 °C … +80 °C | |
Relative air humidity | 95 % r H without condensation | |
Protection rating | IP 20 | |
Certifications | CE, UL | |
UL | ||
Surrounding Air Temperature | 0 °C … +60°C | |
Pollution degree | 2 | |
CE | ||
Noise immunity | DIN EN 61000-6-2 “EMC Immunity” | |
Interference emission | DIN EN 61000-6-4 “EMC Emission” | |
Vibration and shock resistance | DIN EN 60068-2-6:2008 „Vibration“, DIN EN 60068-2-27:2010 „Shock" | |
RoHS | Yes | |
REACH | Yes |
Technical Documentation
Name | Version | Size | Tags | |
---|---|---|---|---|
TB20, Manual Counter 24 V | 3 | 8 MB |
Flyers
Name | Version | Size | Tags | |
---|---|---|---|---|
Flyer, TB20 IO-system for numerous applications | 08-2022 | 6 MB | TB20 IO-system for numerous applications |
Planning Tools
Name | Version | Size | Tags | |
---|---|---|---|---|
1x Zähler 24 V, 500 KHz, 32 Bit, STEP Files | 3 MB | 1x Zähler 24 V, 500 KHz, 32 Bit, STEP Files |