Energy Meter

Energy Meter, 1 A
Energy Meter, 1 A

Energy Meter, 1 A

The energy meter function module can be used to measure all important current and voltage measurement values on 230 V AC networks.

  • Measures current, voltage, power, and energy
  • 1 three-phase or 3 single-phase
  • 3-wire and 4-wire voltage measurements
  • Measures real, reactive, and apparent power and energy
  • Energy meter with gate function; values are storedin the module in a non-volatile manner
  • Configurable process input image table
  • Diagnostic messages
  • Current measurement via 1 A current transformer (secondary current)

The energy meter function module can be used to measure all important current and voltage measurement values on 230 V AC networks. Input voltages (3 phases + N) can be connected directly to the module.
In addition to general status information, the module's configuration can be used to show up to 7 readings in the input image table.
In the event of a system failure, the controllable meter's values will be stored in non-volatile memory.

Parameters for the module

  • Overvoltage / undervoltage threshold
  • Overcurrent threshold
  • Zero transition timeout
  • Enable energy meter
  • 50/60 Hz line frequency
  • 3-wire or 4-wire voltage measurement
  • Process image table input values

Parameters for phases A, B, and C

  • Primary current
  • Secondary current
  • Phase angle error correction (for current transformer phase angle error)
  • Zero crossing, overvoltage / undervoltage , overcurrent diagnoses

Configurable process input image table

  • 7 readings at the same time
  • RMS voltage A,B,C
  • RMS current A,B,C
  • A, B, C, and total real power/energy
  • A, B, C, and total apparent power/energy
  • A, B, C, and total reactive power/energy
  • Frequency
  • A, B, C, and total power factor
  • Phase angle between the voltages or between the currents

Diagnostic messages

  • Phase shift
  • Overvoltage / undervoltage
  • Overcurrent
  • No zero crossing (no phase)
  • Configuration errors

Input currents are coupled through current transformers. The Energy Meter module is designed for a maximum secondary current of 1 A.
Other rated secondary currents, as well as the use of Rogowski coils, are available upon request.

Download PDF datasheet
General information
Order number 600-255-7AA21
Article name Energy Meter, 1 A
Scope of delivery Energy Meter, 1 A
Dimensions (DxWxH) 110 x 25 x 73 mm
Weight Approx. 120 g
Number of inputs Voltage L1, L2, L3, N, Current I1, I2, I3
Voltage Max. 400 V AC
Current Max. 1 A, secondary
from the backplane bus Yes
Diagnoses Undervoltage/overvoltage, Overcurrent, No zero crossing, Phase shift
Parameter configuration length 25/49 bytes
General error indicator Red LED
Internal Max. 150 mA
Power dissipation Max. 2.0 W
Hot-swap capable Yes
Ambient conditions
Ambient temperature 0 °C … +60 °C
Transport and storage temperature -20 °C … +80 °C
Relative air humidity 95 % r H without condensation
Protection rating IP 20
Certifications CE, UL pending
CE
Noise immunity DIN EN 61000-6-2 “EMC Immunity”
Interference emission DIN EN 61000-6-4 “EMC Emission”
Vibration and shock resistance DIN EN 60068-2-8:2008 “Vibration”, DIN EN 60068-27:2010 “Shock“
RoHS Yes
REACH Yes

Technical Documentation

 Name Version Size Tags
TB20, Manual Energy Meter 1 4 MB

Declaration of consent