Analog-input-module, RTD, 16 Bit
8x 2 wire
Analog input modules for the modular fieldbus IO system TB20.
Note: Individual modules cannot be combined with IO systems from other manufacturers.
The scope of delivery already includes the appropriate front connector for the cabling and a base module. The module has 8 analog inputs for RTD resistance measurements with 2 wire.
Parameters for the module
Diagnostic alarm: On | Off
Overflow/underflow diagnosis: On | Off
Representation values: SIMATIC* S7 | SIMATIC* S5
Temperature unit: Celsius x 10 | Fahrenheit x 10 | Kelvin x 10
Parameters for each channel
Wire break detection: On | Off
Interference frequency suppression: None | 10 Hz | 50 Hz | 60 Hz | 400 Hz
Measuring ranges: 150 Ohm | 300 Ohm | 600 Ohm | 3000 Ohm | 6000 Ohm | PT 100 | PT 1000 | Ni 100 | Ni 1000| LGNi 1000
* SIMATIC is a registered trademark of Siemens AG.
- Measuring ranges: 150 ohms, 300 ohms, 600 ohms, 3,000 ohms, 6,000 ohms, Pt100, Pt1000, Ni100, Ni1000, LG-Ni1000, individually configurable for each channel
- Can accommodate 2/3/4-wire sensors
- Measurement resolution: 15 bits + sign
- Diagnostic messages
- Wire break detection
- A bi-color LED (blue/red) indicates the module operating status and any malfunctions
- 2 wire connection
- 8 inputs for resistance measurement, isolated to the backplane bus
- 8 process input words
General information
- Order number600-253-4BH21
- Article nameAI 8 x R, RTD, 16 bit, 2 wire
- Scope of deliveryAI 8 x R, RTD, 16 bit, 2 wire
- Number of inputs8
- InternalMax. 140 mA
- Power dissipationMax. 1 W
- Parameter configuration length10 Bytes
- General error indicatorRed LED
- Hot-swap capableYes
- Hot-swap capableYes
Electrical isolation
- from the backplane busYes
- Between the channelsNo
- Between the channelsNo
Measuring
- Measuring ranges150 Ohm
- 300 Ohm
- 600 Ohm
- 3000 Ohm
- 6000 Ohm
- PT 100
- PT 1000
- Ni 100
- Ni 1000
- LGNi 1000
- PT 100 Klima
- PT 1000 Klima
- Measuring methodIntegration
- Measurement resolution15 bits + sign
- Interference frequency suppressionNone | 10 Hz | 50 Hz | 60 Hz | 400 Hz
- Refresh rate / conversion rateNumber of active channels x conversion time +16 ms for wire break detection for each channel when activated.
- The conversion time will depend on the interference frequency suppression:
- None: 8 ms
- 400 Hz: 45 ms
- 60 Hz: 109 ms
- 50 Hz: 128 ms
- 10 Hz: 342 ms
- DiagnosesUpper measuring range limit exceeded (overflow), lower measuring range limit fallen below (underflow), wire break, parameter assignment error
- Process alarmsUpper and lower limit per channel
Error limits
- Operational error limit in the entire temperature range±0.5 % relative to the nominal range
- Basic error limit at 25 °C±0.3 % relative to the nominal range
- Temperature error±0.005 %/K relative to the nominal range
- Linearity error±0.05 %/K relative to the nominal range
- Repeating accuracy in steady state at 25 °C±0.05 %/K relative to the nominal range
Ambient conditions
- Ambient temperature0 °C … +60 °C
- Transport and storage temperature-20 °C … +80 °C
- Relative air humidity95 % r H without condensation
- Protection ratingIP 20
- CertificationsCE, UL
UL
- Surrounding Air Temperature0 °C … +60°C
- Pollution degree2
CE
- Noise immunityDIN EN 61000-6-2 “EMC Immunity”
- Interference emissionDIN EN 61000-6-4 “EMC Emission”
- Vibration and shock resistanceDIN EN 60068-2-6:2008 „Vibration“, DIN EN 60068-2-27:2010 „Shock"
- RoHSYes
- REACHYes
Name | Version | Size |
TB20, Manual Modules | 15 | 8 MB |
Name | Version | Size |
Flyer, TB20 IO-system for numerous applications | 08-2022 | 6 MB |
Name | Version | Size |
AI 8 x R, RTD, 16 Bit, 2-Draht, STEP Files | 3 MB |