Analoge-output-module, I, 12 Bit
4x
Analog output modules for the modular fieldbus IO system TB20.
Note: Individual modules cannot be combined with IO systems from other manufacturers.
Analog output modules for the modular fieldbus IO system TB20. Note: Individual modules cannot... more
Analoge-output-module, I, 12 Bit 4x
The scope of delivery already includes the appropriate front connector for the cabling and a base module. The module has 4 analogue outputs.
- Output range 0 ... 20 mA, 4 ... 20 mA
- Resolution 12 bit
- Substitute value functionality
- Diagnostic messages
- A bi-color LED (blue/red) indicates the module operating status and any malfunctions
- 4 analog outputs, electrically isolated from the backplane bus
- 4 process output words (4 bytes)
General information
- Order number600-260-4AD01
- Article nameAO 4x I, 0/4 ... 20 mA, 12 bit
- Scope of deliveryAO 4x I, 0/4 ... 20 mA, 12 bit
- Dimensions (DxWxH)110 x 14 x 73 mm
- WeightApprox. 70 g
- Number of outputs4
- Parameter configuration length13 bytes
- General error indicatorRed LED
- Hot-swap capableYes
- Power dissipationMax. 3 W
Output
- Output ranges0 … 20 mA,
- 4 … 20 mA
- Connection for actuators2-wire connection
- Load resistanceMax. 600 ohms
- Inductive loadMax. 100 mH
- No-load voltagemax. 18 V
- Measurement resolution12 bit
- Refresh time0.2 ms
- Settling time0.2 ms for resistive loads,
- 2.2 ms for capacitive loads,
- 0.5 ms for inductive loads (<=1 mH),
- 3.3 ms for inductive loads (<=3.3 mH)
- DiagnosesExternal reference voltage missing (L+), wire break, parameter assignment error
- Process alarmsUpper and lower limit per channel
- Process alarmsUpper and lower limit per channel
Electrical isolation
- from the backplane busYes
- Between the channelsNo
Current draw
- ExternalMax. 100 mA
- InternalMax. 26 mA
Error limits
- Operational error limit in the entire temperature range±0.5 % relative to the nominal range
- Basic error limit at 25 °C±0.3 % relative to the nominal range
- Temperature error±0.005 %/K relative to the nominal range
- Linearity error±0.05 %/K relative to the nominal range
- Repeating accuracy in steady state at 25 °C±0.05 %/K relative to the nominal range
- Repeating accuracy in steady state at 25 °C±0.05 %/K relative to the nominal range
Ambient conditions
- Ambient temperature0 °C … +60 °C
- Transport and storage temperature-20 °C … +80 °C
- Relative air humidity95 % r H without condensation
- Protection ratingIP 20
- CertificationsCE, UL
UL
- Surrounding Air Temperature0 °C … +60°C
- Pollution degree2
CE
- Noise immunityDIN EN 61000-6-2 “EMC Immunity”
- Interference emissionDIN EN 61000-6-4 “EMC Emission”
- Vibration and shock resistanceDIN EN 60068-2-6:2008 „Vibration“, DIN EN 60068-2-27:2010 „Shock"
Name | Version | Size |
TB20, Manual Modules | 15 | 8 MB |
Name | Version | Size |
Flyer, TB20 IO-system for numerous applications | 08-2022 | 6 MB |
Name | Version | Size |
AO 4 x I, 0/4...20 mA, 12 Bit, STEP Files | 3 MB |