Analoge-output-module, U, 12 Bit
2x
Analog output modules for the modular fieldbus IO system TB20.
Note: Individual modules cannot be combined with IO systems from other manufacturers.
Analog output modules for the modular fieldbus IO system TB20. Note: Individual modules cannot... more
Analoge-output-module, U, 12 Bit 2x
The scope of delivery already includes the appropriate front connector for the cabling and a base module. The module has 2 analogue outputs.
- Output range ±10 V, 0–10 V, 1–5 V
- Resolution 11 bit + sign
- Substitute value functionality
- Diagnostic messages
- A bi-color LED (blue/red) indicates the module operating status and any malfunctions
- 2 analog outputs, electrically isolated from the backplane bus
- 2 process output words (4 bytes)
General information
- Order number600-261-4AB01
- Article nameAO 2 x U, ±10 V, 0–10 V, 1–5 V, 12 bit
- Scope of deliveryAO 2 x U, ±10 V, 0–10 V, 1–5 V, 12 bit
- Dimensions (DxWxH)110 x 14 x 73 mm
- WeightApprox. 70 g
- Parameter configuration length7 bytes
- General error indicatorRed LED
- Hot-swap capableYes
- Hot-swap capableYes
Output
- Number of outputs2
- Measurement resolution11 bit + sign
- Refresh time0.2 ms
- Settling time0.2 ms for resistive loads, 2.2 ms for capacitive loads, 0.5 ms for inductive loads (<=1 mH), 3.3 ms for inductive loads (<=3.3 mH)
- DiagnosesExternal reference voltage missing (L+), short circuit to GND, parameter assignment error
- Output ranges±10 V,
- 0–10 V,
- 1–5 V
- Power dissipationMax. 1.6 W
- Connection for actuators2-wire connection
- Load resistanceMin. 1 kohm
- Capacitive loadMax. 1 µF
Electrical isolation
- from the backplane busYes
- Between the channelsNo
Current draw
- ExternalMax. 45 mA
- InternalMax. 24 mA
- InternalMax. 24 mA
Short-circuit protection
- Short-circuit protectionYes
- Short-circuit currentMax. 25 mA
Error limits
- Operational error limit in the entire temperature range±0.5 % relative to the nominal range
- Basic error limit at 25 °C±0.3 % relative to the nominal range
- Temperature error±0.005 %/K relative to the nominal range
- Linearity error±0.05 %/K relative to the nominal range
- Repeating accuracy in steady state at 25 °C±0.05 %/K relative to the nominal range
Ambient conditions
- Ambient temperature0 °C … +60 °C
- Transport and storage temperature-20 °C … +80 °C
- Relative air humidity95 % r H without condensation
- Protection ratingIP 20
- CertificationsCE, UL
UL
- Surrounding Air Temperature0 °C … +60°C
- Pollution degree2
CE
- Noise immunityDIN EN 61000-6-2 “EMC Immunity”
- Interference emissionDIN EN 61000-6-4 “EMC Emission”
- Vibration and shock resistanceDIN EN 60068-2-6:2008 „Vibration“, DIN EN 60068-2-27:2010 „Shock"
Name | Version | Size |
TB20, Manual Modules | 15 | 8 MB |
Name | Version | Size |
Flyer, TB20 IO-system for numerous applications | 08-2022 | 6 MB |
Name | Version | Size |
AO 2x U, ±10 V, 0-10 V, 1-5 V, 12 Bit, STEP Files | 3 MB |