Analog-input-module, TC, Iso., 16 Bit
4x

Analog input modules for the modular fieldbus IO system TB20.
Note: Individual modules cannot be combined with IO systems from other manufacturers.
The scope of delivery already includes the appropriate front connector for the cabling and a base module. The module has 4 analog inputs for connecting thermocouples.
Parameters for the module
Diagnostic alarm: On | Off
Overflow/underflow diagnosis: On | Off
Representation values: SIMATIC* S7 | SIMATIC* S5 (for ±80 mV only)
Temperature unit: Celsius x 10 | Fahrenheit x 10 | Kelvin x 10
Parameters for each channel
Wire break detection: On | Off
Interference frequency suppression: None | 10 Hz | 50 Hz | 60 Hz | 400 Hz
Measuring ranges: ±80 mV
Thermocouples: E | J | K | N | R | S | T | B | C | L
Temperature compensation: Internal | External | Process data-based
Limit value alarms enabled: On | Off
Upper/lower limit: 16 bit analog value (±27648)
* SIMATIC is a registered trademark of Siemens AG.
- Measuring range ±80 mV
- Supported thermocouples: E, J, K, N, R, S, T, B, C, L
- Measurement resolution: 15 bits + sign
- External or internal temperature compensation
- Wire break detection
- Diagnostic messages
- Limit value alarms for each channel
- A bi-color LED (blue/red) indicates the module operating status and any malfunctions
- Red/green bi-color LEDs (one for each channel) indicate the channel status
- 4 inputs, electrically isolated from the backplane bus
- 4 process input words
- 4 process output words (for temperature compensation)
General information
- Order number600-254-4AD02
- Article nameAI 4x TC, Iso., 16 bit
- Scope of deliveryAI 4x TC, Iso., 16 bit
- Dimensions (DxWxH)110 x 14 x 73 mm
- WeightApprox. 70 g
- Number of inputs4
- InternalMax. 95 mA
- Power dissipationMax. 0.7 W
- Parameter configuration length26 bytes
- General error indicatorRed LED
- Hot-swap capableYes
- Hot-swap capableYes
Electrical isolation
- from the backplane busYes
- Between the channelsYes
Measuring
- Measuring ranges± 80 mV
- ThermocouplesE (-270 °C … 990 °C)
- J (-210 °C ... 1200 °C)
- K (-270 °C … 1380 °C)
- N (-270 °C … 1320 °C)
- R (-50 °C … 1775 °C)
- S (-50 °C … 1775 °C)
- T (-270 °C … 405 °C)
- B (0 °C … 1800 °C)
- C (0 °C … 2320 °C)
- L (0 °C … 900 °C)
- Measuring methodIntegration
- Measurement resolution15 bits + sign
- Interference frequency suppressionNone | 10 Hz | 50 Hz | 60 Hz | 400 Hz
- Refresh rate / conversion rateDepends on the interference frequency suppression setting being used:
- None: 2.5 ms
- 400 Hz: 8 ms
- 60 Hz: 51 ms
- 50 Hz: 60 ms
- 10 Hz: 160 ms
- DiagnosesUpper measuring range limit exceeded (overflow), lower measuring range limit fallen below (underflow), parameter assignment error
- Process alarmsUpper and lower limit per channel
Error limits
- Operational error limit in the entire temperature range±0.5 % relative to the nominal range
- Basic error limit at 25 °C±0.3 % relative to the nominal range
- Temperature error±0.005 %/K relative to the nominal range
- Linearity error±0.05 %/K relative to the nominal range
- Repeating accuracy in steady state at 25 °C±0.05 %/K relative to the nominal range
Ambient conditions
- Ambient temperature0 °C … +60 °C
- Transport and storage temperature-20 °C … +80 °C
- Relative air humidity95 % r H without condensation
- Protection ratingIP 20
- CertificationsCE, UL
UL
- Surrounding Air Temperature0 °C … +60°C
- Pollution degree2
CE
- Noise immunityDIN EN 61000-6-2 “EMC Immunity”
- Interference emissionDIN EN 61000-6-4 “EMC Emission”
- Vibration and shock resistanceDIN EN 60068-2-6:2008 „Vibration“, DIN EN 60068-2-27:2010 „Shock"
Name | Version | Size |
TB20, Manual Modules | 15 | 8 MB |
Name | Version | Size |
Flyer, TB20 IO-system for numerous applications | 08-2022 | 6 MB |
Name | Version | Size |
AI 4x TC, Iso., 16 Bit, STEP Files | 3 MB |