PROFINET Coupler
DP / PN

Machines and systems can be linked with fieldbus couplers. This makes data exchange between different control worlds possible. A complex CPU-to-CPU communication can be omitted. Depending on the fieldbus, the integration takes place via device description files such as GSD, GSDML or EDS.
With the new DP/PN Coupler, a simple and uncomplicated connection of PROFIBUS to PROFINET is possible. It allows data transfer between a PROFIBUS master and a PROFINET controller. The maximum size of the transmitted data is 244 bytes of input data and 244 bytes of output data. The DP/PN Coupler is projected via a GSD file on the PROFIBUS side and a GSDML file on the PROFINET side. No additional configuration software is necessary.
- Very compact design for DIN rail mounting
- Exchange of up to 244 bytes I/O data
- Redundant power supply
- Galvanic separation of the networks
- No influencing of the opposite side in the event of bus system failure
- Setting of the PROFIBUS addresses using DIP switches or software
- Configuration just with GSD/GSDML file
General information
- Order number700-158-3DP02
- Article nameDP/PN Coupler
- Scope of deliveryDP/PN Coupler with power supply plug
- Dimensions (DxWxH)32.5 x 58.5 x 76 mm
- Weightapprox. 135 g
PROFINET interface (X1)
- Number1
- Connection2x RJ45, integrated switch
- ProtocolPROFINET IO Device as defined in IEC 61158-6-10
- Transmission rate100 Mbps full duplex
- FeaturesMedia Redundancy Protocol (MRP)
- automatic addressing
- topology detection (LLDP, DCP)
- diagnosis alarm
- PROFINET conformance class B
PROFIBUS interface
- ProtocolPROFIBUS-DP
- Connection9-pin D-sub female connector
- Transmission ratemax. 12 Mbps, autom. detection
- I/O image sizemax. 244 bytes of input / 244 bytes of output data
Status indicator
- Function status9 LEDs
- Ethernet status4 LEDs
Power supply
- Operating voltage24 V DC (18 ... 28 V DC)
- Current drawmax. 160 mA
- Power dissipationmax. 3.9 W
Ambient conditions
- Ambient temperature0 °C to 60 °C
- Transport and storage temperature-20 °C to 80 °C
- Relative air humidity95 % r H without condensation
- Protection ratingIP 20
- Mounting positionas desired
Compliance
- ApprovalsCE, UL
- RoHSYes
- REACHYes
UL
- ULUL 61010-1 / UL 61010-2-201
- Voltage supplyDC 24 V (18 ... 28 VDC, SELV and limited energy circuit)
- Pollution degree2
- AltitudeUp to 2000m
- Temperature cable rating87 °C
Name | Version | Size |
DP/PN Coupler V2, Quick Start Guide | 9 | 1 MB |
DP/PN Coupler V2, PROFINET-Certificate | 82 KB | |
EU Declaration of Confirmity | 04-2020 | 51 KB |
Name | Version | Size |
DP/PN Coupler - PROFIBUS PROFINET easily connected | 11-2019 | 586 KB |
Easy connection of fieldbus networks – with Helmholz PROFINET gateways | 11-2021 | 1 MB |
Name | Version | Size |
DP/PN Coupler, license terms | 314 KB |
Name | Version | Size |
IPSet | 1.04.016 | 23 MB |
DP/PN Coupler, GSDML file for 700-158-3DP01 (V1) and 700-158-3DP02 (V2) | 20200909 | 8 KB |
DP/PN Coupler, GSD file for 700-158-3DP02 (V2) | V2.01 | 9 KB |
DP/PN Coupler, Firmware for 700-158-3DP02 (V2) | V2.02.010 | 7 MB |
DP/PN Coupler, GSD file for 700-158-3DP01 (V1) | V1.00 | 8 KB |
Name | Version | Size |
DP/PN Coupler, STEP files | 3 MB | |
DP/PN Coupler, macros for EPLAN | 11 MB | |
DP/PN Coupler V2, STEP files | 3 MB |