Analog-input-module, RTD, 16 Bit
1 / 2x R

Analog input modules for the modular fieldbus IO system TB20.
Note: Individual modules cannot be combined with IO systems from other manufacturers.
The scope of delivery already includes the appropriate front connector for the cabling and a base module. The module has 1 to 2 analog inputs for RTD resistance measurements, depending on whether the wiring is 2 / 3 / 4 wire.
Parameters for the module
Diagnostic alarm: On | Off
Overflow/underflow diagnosis: On | Off
Representation values: SIMATIC* S7 | SIMATIC* S5
Temperature unit: Celsius x 10 | Fahrenheit x 10 | Kelvin x 10
Parameters for each channel
Wire break detection: On | Off
Interference frequency suppression: None | 10 Hz | 50 Hz | 60 Hz | 400 Hz
Measuring ranges: 150 ohms / 300 ohms / 600 ohms / 3000 ohms / 6000 ohms / PT100 / PT1000 / Ni100 / Ni1000 / LGNi1000
Sensor type: Disabled | 2-wire | 3-wire (channel 0 only) | 4-wire (channel 0 only)
Limit value alarms enabled: On | Off
Upper/lower limit: 16 bit analog value (±27648)
* SIMATIC is a registered trademark of Siemens AG.
- Measuring ranges: 150 ohms, 300 ohms, 600 ohms, 3,000 ohms, 6,000 ohms, Pt100, Pt1000, Ni100, Ni1000, LG-Ni1000, individually configurable for each channel
- Can accommodate 2/3/4-wire sensors
- Measurement resolution: 15 bits + sign
- Diagnostic messages
- Wire break detection
- A bi-color LED (blue/red) indicates the module operating status and any malfunctions
- Can accommodate 2/3/4-wire sensors
- Limit value alarms for each channel
- 1/2 inputs for measuring resistance, electrically isolated from the backplane bus
- 2 process input words
General information
- Order number600-253-4AB01
- Article nameAI 1/2x R, RTD, 16 bit, 2/3/4 wire
- Scope of deliveryAI 1/2x R, RTD, 16 bit, 2/3/4 wire
- Dimensions (DxWxH)110 x 14 x 73 mm
- WeightApprox. 70 g
- Number of inputs1/2
- InternalMax. 140 mA
- Power dissipationMax. 1 W
- Parameter configuration length14 bytes
- General error indicatorRed LED
- Hot-swap capableYes
- Hot-swap capableYes
Electrical isolation
- from the backplane busYes
- Between the channelsNo
Measuring
- Measuring ranges150 ohms,
- 300 ohms,
- 600 ohms,
- 3000 ohms,
- 6000 ohms,
- PT100,
- PT1000,
- Ni100,
- Ni1000,
- LGNi1000
- Measuring methodIntegration
- Measurement resolution15 bits + sign
- Interference frequency suppressionNone | 10 Hz | 50 Hz | 60 Hz | 400 Hz
- Refresh rate / conversion rateNumber of active channels x conversion time +16 ms for wire break detection for each channel when activated.
- The conversion time will depend on the interference frequency suppression:
- None: 8 ms
- 400 Hz: 45 ms
- 60 Hz: 109 ms
- 50 Hz: 128 ms
- 10 Hz: 342 ms
- DiagnosesUpper measuring range limit exceeded (overflow), lower measuring range limit fallen below (underflow), wire break, parameter assignment error
- Process alarmsUpper and lower limit per channel
Error limits
- Operational error limit in the entire temperature range±0.5 % relative to the nominal range
- Basic error limit at 25 °C±0.3 % relative to the nominal range
- Temperature error±0.005 %/K relative to the nominal range
- Linearity error±0.05 %/K relative to the nominal range
- Repeating accuracy in steady state at 25 °C±0.05 %/K relative to the nominal range
Ambient conditions
- Ambient temperature0 °C … +60 °C
- Transport and storage temperature-20 °C … +80 °C
- Relative air humidity95 % r H without condensation
- Protection ratingIP 20
- CertificationsCE, UL
UL
- Surrounding Air Temperature0 °C … +60°C
- Pollution degree2
CE
- Noise immunityDIN EN 61000-6-2 “EMC Immunity”
- Interference emissionDIN EN 61000-6-4 “EMC Emission”
- Vibration and shock resistanceDIN EN 60068-2-6:2008 „Vibration“, DIN EN 60068-2-27:2010 „Shock"
- RoHSYes
- REACHYes
Name | Version | Size |
TB20, Manual Modules | 15 | 8 MB |
Name | Version | Size |
Flyer, TB20 IO-system for numerous applications | 08-2022 | 6 MB |
Name | Version | Size |
AI 1/2x R, RTD, 16 Bit, 2/3/4-Draht, STEP Files | 3 MB |